Neutropenic & Infection Patient Isolation Rooms

 

Metisafe® Neutropenic & Infection Patient Isolation Rooms

  • Negative pressure (Infection Chamber)
  • Positive pressure (Neutropenic Air Chamber)
  • HEPA filtration (0,3 μm, %99,97)
  • air conditioning with air recirculation
  • Negative plenum technology
  • Zero leakage HEPA Filter
FILTRATION
FRESH AIR
  • G4 panel type pre-filter,
  • F7 V-type pre-filter,
  • HEPA filter
PATIENT ROOM
  • F7 cassette type pre-filter,
  • H13 HEPA filter
HEATING-COOLING
PATIENT ROOM
  • COld/Warm water, electrical heater,
  • UV inactivation system,
  • Air-mix compartment,
  • Condensation prevented unpassaged heating featured flat isolation panel,
  • Easy cleaning surface heating/cooling units,
  • Heating/Cooling power min. 5000 Watt
AUTOMATION SYSTEM/SENSORS
CONTROL PARAMETERS
  • 5,7 Inch touch sensitive screen PLC control panel: Continuous measurement of temperature,
  • Pressure, air flow rate controlled by sensors.
  • Energy saving through Day and Night (Eco) mode run.
TEMPERATURE SENSOR
  • RS 485 connected hygienic wall type temperature and humidity sensor
PRESSURE SENSOR
  • Micro type pressure key performs between 7-15 Pa measurement
AIR FLOW MEASUREMENT
  • Average air flow rate measurement by rotor type air flow velocity sensor
ALARMS
PRESSURE
  • Activated at room pressure under 8 Pa
AIR FLOW RATE
  • Alarm activation at ACH ≤ 5
QUALITY AND CERTIFICATES
SERTİFİKALAR
  • CE
  • Management certificate of ISO9001
  • ISO 14644 Clean Room class compatibility
  • EN61010 Electrical and Electronic safety compatibility
  • Accredited test company validation guarantee (When installation made by Metis or by its certified technical personnel)
VENTILATION
SPECIFICATIONUNITRATEDESCRIPTION
FRESH AIR FLOW RATEm3/saat1000-1400Nominal rate is 1200 m3/h. Adjustable.
ACHACH (1/saat)≥ ACH 3Air change per hour (ACH) is kept at minimum 3.
TOTAL AIRm3/saat2000-2800Nominal rate is 2400 m3/h. Adjustable.
TOTAL AIR CHANGE PER HOURACH (1/Hour)≥ ACH 10Nominal rate of ACH = 12
RECIRCULATION AIR FLOW RATEm3/Hour1200-2000 
AIR FLOW TYPE AND DIRECTIONLaminar air flow over patient bed, turbulent air flow type at rest of the room, hybrid air flow type is applied. Filtered air directs from the ceiling and sucked through by 2 different positioned culvers at the bottom.
EXHAUST AIR DUCT AIR FLOW RATEm3/Hour1500-2500Air exhausted through air ducts to the atmosphere. Exhaust air ducts are kept at min 15 Pa negative pressure.